The PT-G510 Series is designed to deliver the highest level of system availability and data integrity for mission-critical applications in digital
substations that demand zero-recovery-time redundancy. The PT-G510 Series supports PRP/HSR to achieve seamless redundancy for substations
and process automation systems. Hardware-based IEEE 1588v2 PTP is also supported for time-critical applications. Featuring a highly durable
design, the PT-G510 Series is certified for IEC 61850-3 Edition 2 Class 2 to fulfill demanding requirements in substation applications.
The PT-G510 Series comes with eight 100/1000BaseT(X) Ethernet ports or 100/1000BaseSFP slots with two dedicated 100/1000BaseSFP PRP/
HSR ports combined with support for a complete redundancy protocol suite including PRP, HSR, MRP, STP, MSTP, and RSTP for maximum
network reliability. The PT-G510 Series further supports GOOSE Check to efficiently monitor GOOSE packets and features a built-in MMS server
based on IEC 61850-90-4 switch data modeling for power SCADA systems.
- IEC 61850-3 Edition 2 Class 2 compliant
- IEC 62439-3 Clause 4 (PRP) and Clause 5 (HSR) compliant
- IEEE 1588 hardware time stamp supported
- Supports IEEE C37.238 and IEC 61850-9-3 power profiles
- GOOSE Check for easy troubleshooting
- Built-in MMS server based on IEC 61850-90-4 switch data modeling for power SCADA
- -40 to 75°C operating temperature range